Socomec DIRIS A40 / A41 RS485 Modbus Register Map

The Socomec DIRIS A40 / A41 RS485 is a power meter used for power monitoring, energy metering, and facility automation. This page provides a sample Modbus register map with addresses, data types, and signal categories to help engineers commission, troubleshoot, and monitor the device. For Socomec DIRIS A40 / A41 RS485 deployments, teams often use this map to surface harmonics, power, and voltage data in facility metering, commissioning, and operational analytics.

This page shows a preview subset of the full device map available in Modbus Monitor XPF.

Engineers searching for Socomec DIRIS A40 / A41 RS485 Modbus map, Socomec DIRIS A40 / A41 RS485 register map, or Socomec DIRIS A40 / A41 RS485 Modbus registers can use this page as a compatibility snapshot before importing the full map into Modbus Monitor XPF. Also aligns to search intent around Socomec DIRIS A40 / A41 RS485 Modbus register list, Socomec DIRIS A40 / A41 RS485 Modbus table.

Overview

  • Device: Socomec DIRIS A40 / A41 RS485
  • Type: Power Meter
  • Protocol: Modbus RTU / Modbus TCP
  • Use case: power monitoring, energy metering, and facility automation
  • Works with: Modbus Monitor XPF (import directly)

Download Modbus Map

The full Socomec DIRIS A40 / A41 RS485 Modbus register map is available inside Modbus Monitor XPF as a pre-built device map. Download the free feature-locked version to access and export the complete map.

Register Table (Sample)

Sample registers from the Socomec DIRIS A40 / A41 RS485 Modbus map. Import the full map in Modbus Monitor XPF to access all registers.

Signal Address Type Units Category
Phase to phase voltage u12 V 410513 UINT32 V Voltage
Phase current 1 410527 UINT32 - Current
active power kW 410535 UINT32 kW Power
Active energy 410769 UINT32 kWh Energy
Frequency Hz 410525 UINT32 Hz Frequency
Internal temperature sensor present 411455 UINT16 degC Temperature
Thd u12 411535 UINT16 - Harmonics
Hour meter 1 410511 UINT32 - General
Phase to phase voltage u23 V 410515 UINT32 V Voltage
Phase to phase voltage u31 V 410517 UINT32 V Voltage
Phase to neutral voltage phase 1 V 410519 UINT32 V Voltage
Phase to neutral voltage phase 2 V 410521 UINT32 V Voltage

How to Use This Map

  1. Download Modbus Monitor XPFGet the free version.
  2. Select the Socomec DIRIS A40 / A41 RS485 device map — pre-built maps are bundled and ready to load.
  3. Connect to your device — enter the device IP or COM port and start polling registers immediately.
  4. Visualise and log — build dashboards, trend data, and export readings without manual register entry.

Why Use Pre-Built Maps

  • Saves time — no need to manually look up or enter register addresses
  • Reduces errors — pre-validated maps eliminate mis-typed addresses and wrong data types
  • Speeds commissioning — connect and poll within minutes instead of hours
  • Reusable across projects — use the same map across multiple sites and installations

Data Categories Available

  • Harmonics
  • Power
  • Voltage
  • Current
  • Temperature
  • Frequency