Accuenergy Acuvim II Modbus Register Map¶
The Accuenergy Acuvim II is a power meter used for power monitoring, energy metering, and facility automation. This page provides a sample Modbus register map with addresses, data types, and signal categories to help engineers commission, troubleshoot, and monitor the device. For Accuenergy Acuvim II deployments, teams often use this map to surface power, energy, and current data in multi-circuit energy monitoring, tenant billing, and branch circuit analytics.
This page shows a preview subset of the full device map available in Modbus Monitor XPF.
Engineers searching for Accuenergy Acuvim II Modbus map, Accuenergy Acuvim II register map, or Accuenergy Acuvim II Modbus registers can use this page as a compatibility snapshot before importing the full map into Modbus Monitor XPF.
Overview¶
- Device: Accuenergy Acuvim II
- Type: Power Meter
- Protocol: Modbus RTU / Modbus TCP
- Use case: power monitoring, energy metering, and facility automation
- Works with: Modbus Monitor XPF (import directly)
Download Modbus Map¶
The full Accuenergy Acuvim II Modbus register map is available inside Modbus Monitor XPF as a pre-built device map. Download the free feature-locked version to access and export the complete map.
Register Table (Sample)¶
Sample registers from the Accuenergy Acuvim II Modbus map. Import the full map in Modbus Monitor XPF to access all registers.
| Signal | Address | Type | Units | Category |
|---|---|---|---|---|
| Voltage Input Wiring Type 0 3LN 1 1LN 2 2LL 3 3LL 4 1LL | 404100 | UINT16 | V | Voltage |
| Current Input Wiring Type 0 3CT 1 1CT 2 2CT | 404101 | UINT16 | - | Current |
| Reactive Power Calculation Method 0 True Reactive Power 1 Generic Reactive Power | 404121 | UINT16 | kW | Power |
| kWh Pulse Constant 1 60000 | 404107 | UINT16 | kWh | Energy |
| Frequency Selection 0 50Hz 1 60Hz | 404094 | UINT16 | Hz | Frequency |
| VAR PF Convention 0 IEC 1 IEEE | 404118 | UINT16 | - | Power Factor |
| Demand Interval 1 30 | 404110 | UINT16 | kW | Demand |
| Seal Status 0x0A Sealed Other Unsealed | 404128 | UINT16 | - | Status |
| THD V1 V12 THD Rx 100 | 416475 | INT16 | - | Harmonics |
| Channel 1 Communication Protocol 0 Modbus 2 BACnet MS TP | 404095 | UINT16 | - | Communication |
| Channel 1 Parity 0 Even 1 Odd 2 None2 3 None1 | 404096 | UINT16 | - | General |
| kvarh Pulse Constant 1 60000 | 404108 | UINT16 | kWh | Energy |
How to Use This Map¶
- Download Modbus Monitor XPF — Get the free version.
- Select the Accuenergy Acuvim II device map — pre-built maps are bundled and ready to load.
- Connect to your device — enter the device IP or COM port and start polling registers immediately.
- Visualise and log — build dashboards, trend data, and export readings without manual register entry.
Why Use Pre-Built Maps¶
- Saves time — no need to manually look up or enter register addresses
- Reduces errors — pre-validated maps eliminate mis-typed addresses and wrong data types
- Speeds commissioning — connect and poll within minutes instead of hours
- Reusable across projects — use the same map across multiple sites and installations
Data Categories Available¶
- Power
- Energy
- Current
- Voltage
- Harmonics
- Status